CN

S-FLS-2-5G

This SPD limits induced transients of different origin (lightning stroke, switching impulse, etc.). This is achieved by diverting the transient current to ground and limiting the signal line voltage to a safe level for the duration of the surge. It can be applied to 2 wire RTD,TC,RS-485,MODBUS,PROFIBUSDP,CAN ect.

Type

Wire system

Ex

Ground protection

Share
S-FLS-2-5G

【Core technology】

s-fls.png.jpg

【Installation and disposal】



15719913382876999Yxm.gif1571991347588242JgtX.gif

                                    

Installation                                               Disposal 



General parameters
標(biāo)稱電壓Un 5 V
直流最大持續(xù)工作電壓Uc 6 V
交流最大持續(xù)工作電壓Uc 4 V
通用標(biāo)稱電流IL 600 mA
串聯(lián)阻抗 1.8 Ω
響應(yīng)時(shí)間Ta < 1 ns
頻寬fG 100 MHz
雷電參數(shù)
總雷電沖擊電流Iimp(10/350 μs),D1 5 kA
每線雷電沖擊電流Iimp(10/350 μs),D1 2.5 kA
最大放電電流Imax(8/20 μs),C2 20 kA
每線標(biāo)稱放電電流In(8/20 μs),C2 10 kA
保護(hù)電壓Up(8/20 μs),C2 L – L ≤ 45 V/ L – PE ≤ 45 V
保護(hù)電壓Up(1 kV/μs),C3 L – L ≤ 15 V/ L – PE ≤ 15 V
Operating conditions
工作溫度范圍 -40 ℃ ~ +80 ℃
外殼材料
外殼材料 PC
阻燃等級(jí)(UL94) V0
防護(hù)等級(jí) IP20
Mechanical specifications
最小安裝導(dǎo)線截面積 0.2 mm2
最大安裝導(dǎo)線截面積 2.5 mm2
安裝方式 DIN35 mm導(dǎo)軌安裝
接地方式 導(dǎo)軌接地/端子接地(選配)
Certified data
測(cè)試標(biāo)準(zhǔn) IEC 61643-21/GB/T 18802.21
產(chǎn)品認(rèn)證 SIL, CE, FCC, 防雷
設(shè)備類型 Type A
硬件故障裕度(HFT) 0
操作模式 低/高
安全完整性等級(jí) SIL3
λS (1 FIT=10-9/h) 9.40 FIT
λDU (1 FIT=10-9/h) 0.464 FIT
λDD (1 FIT=10-9/h) 0 FIT
λTOTAL (1 FIT=10-9/h) 9.864 FIT
SFF 95.3%
PFDavg(T1=1Y) 2.03E-06
PFH 4.60E-10 1/h
NPEXA-C11

一入一出

熱電偶輸入安全柵